Battery runtime maths and the Peukert effect
In one line: Calculate backup minutes from Ah, voltage, series and parallel layout, efficiency and depth of discharge, then correct for Peukert.
UPS runtime starts from "energy in the battery divided by the load", but the real answer is always shorter. Losses and discharge behaviour explain the gap.
The basic energy calculation
One 12 V 9 Ah battery holds 108 Wh in theory. A 24 V pack is two 12 V batteries in series, so voltage doubles, capacity stays 9 Ah and energy is 216 Wh. In parallel, capacity adds and voltage stays the same.
total Wh = Ah * nominal V * series * parallel
usable Wh = total Wh * DoD * (1 - aging)
runtime min = usable Wh * inverter efficiency / load W * 60
Take two 12 V 9 Ah batteries in series (24 V, 9 Ah), 80% depth of discharge, 20% aging, 85% inverter efficiency and a 150 W load. Usable energy is 216 * 0.8 * 0.8 = 138 Wh; at the inverter input that is 123 Wh; runtime is about 49 minutes.
The Peukert effect
The Ah rating is usually quoted at the 20-hour rate, meaning a 9 Ah battery delivers 9 Ah when discharged at 0.45 A for 20 hours. Pull a larger current and the chemistry cannot keep up, so the usable capacity shrinks. Peukert's equation describes this.
t = H * (C / (I * H))^k
H: reference hours (20), C: rated Ah, I: discharge current, k: Peukert exponent
Typical exponents are 1.1 to 1.3 for flooded lead-acid, around 1.15 for AGM and VRLA, and 1.02 to 1.08 for LiFePO4. An exponent of 1 is an ideal battery with no capacity loss. In the example, the DC current at 150 W is 150 / 0.85 / 24, about 7.35 A. At that current the 20-hour capacity gives 1.2 hours, but with k = 1.15 the equation gives 20 * (9 / (7.35 * 20))^1.15, about 0.63 hours, so 38 minutes rather than 49.
| Load | DC current | Linear estimate | Peukert, k=1.15 | Difference |
|---|---|---|---|---|
| 50 W | 2.45 A | 148 min | 137 min | -7% |
| 150 W | 7.35 A | 49 min | 38 min | -22% |
| 300 W | 14.7 A | 25 min | 17 min | -32% |
Constant power versus constant current
An inverter holds output voltage steady, so as the battery voltage sags it draws more current to deliver the same watts. A pure resistive load draws less current as voltage falls. That is why the constant power model yields a shorter runtime. The calculator assumes an average discharge voltage of 94% of nominal to account for this.
Temperature and aging
Lead-acid capacity is rated at 25 degrees Celsius. At 0 degrees it drops 10 to 20%, and at minus 10 it can drop more than 30%. Above 35 degrees capacity rises but life may halve. For a battery older than three years, assume only 60 to 70% of rated capacity remains.
Why vendor charts differ
Vendor runtime charts are measured on new batteries at 25 degrees, with a fixed load, down to a specified cutoff voltage. Add aging, cold, and a high load ratio and a 10 to 30% shorter result is normal. Plan on 70% of the calculated number as the runtime you can actually rely on.
The calculator runs right here in your browser. Your device list is not saved.
Back to the UPS calculatorFrequently asked questions
Can I work out runtime from Ah alone?
No. You also need voltage and layout, load watts, inverter efficiency and depth of discharge. The same 9 Ah is twice the energy at 24 V as at 12 V, and Peukert losses grow with the load.
Do lithium batteries need Peukert correction?
The effect is smaller but real. LiFePO4 has an exponent around 1.02 to 1.08, so capacity loss at high load is roughly 5%. You also have to respect the BMS low-voltage cutoff and temperature limits.
Does adding external batteries scale runtime linearly?
Broadly yes, within limits. Parallel capacity adds runtime in theory, but charge time grows, inverter efficiency falls at light loads, and small UPS units cannot recharge a large bank quickly. Stay inside the manufacturer's expansion limits.
Sources
- Wikipedia — Peukert's law
- Battery University — Discharging at high and low temperatures
- Wikipedia — Lead-acid battery
Read next
- VA, watts and power factor on a UPS nameplateWhy a UPS lists both VA and watts, what a low power factor does to the rating you need, and how to read the numbers.
- Sizing a UPS for a home lab and NASUse real measured watts from your NAS, router, mini PC and switch to choose UPS capacity and headroom without overspending.
- UPS batteries: lead-acid versus LiFePO4Compare VRLA and AGM lead-acid with LiFePO4 lithium for UPS use: cycle life, usable depth, temperature, safety and cost.