From UPS size to backup minutes, in real numbers
Enter each device's real power draw and UpsCalc adds it up, converts watts to apparent power at your power factor, applies peak headroom and recommends a standard UPS rating. The same page estimates battery backup time from capacity and inverter efficiency, plus monthly and yearly electricity cost and CO2 for that load.
In one line: UpsCalc is a free UPS and home lab power calculator that runs only in your browser. The device list you type is never sent anywhere.
- 3calculators (size, runtime, cost)
- 0.5–1.0power factor range
- 20guides (4 languages)
- 0uploads
UPS sizing (VA ↔ W)
Add up the real watts each device draws, divide by the power factor to get apparent power in VA, then add peak headroom to reach a design load. Enter your UPS rating to see the load ratio and whether it would be overloaded.
Presets
Device list
| Device | Watts | Qty | Subtotal (W) | |
|---|---|---|---|---|
| 40 | ||||
| 12 | ||||
| 15 | ||||
| 45 | ||||
| 16 |
Sizing result
| Total real power | 128 W |
|---|---|
| Total apparent power | 182.9 VA |
| Design size (with headroom) | 228.6 VA |
| Design real load | 160 W |
| Recommended standard rating | 350 VA |
| Load ratio (VA / W) | 36.6% / 28.4% |
| Verdict | Comfortable |
A 40–70% load ratio is the sweet spot. Above 85% runtime collapses during an outage, and above 100% the UPS may cut off immediately.
Real load margin at that rating: 322 W
Battery backup runtime
Battery capacity, voltage and series/parallel layout, inverter efficiency, usable depth of discharge and aging all change the answer. Turn on Peukert correction to model the capacity lost at high discharge currents.
| Battery energy | 2,400 Wh |
|---|---|
| Usable energy | 1,536 Wh |
| DC discharge current | 7.82 A |
| Estimated backup time | 7h 9min |
| Battery capacity needed | 9.9 Ah |
Method comparison
| Method | Minutes | Hours |
|---|---|---|
| Linear energy method | 522 | 8h 42min |
| Peukert corrected | 429 | 7h 9min |
Assumptions and limits
- The Peukert exponent defaults to 1.15 for VRLA and AGM, around 1.05 for LiFePO4. An exponent of 1 means an ideal battery with no capacity loss at high current.
- The constant power model derives current from an average discharge voltage of 94% of nominal. A real inverter pulls more current as voltage sags, so runtime can come out shorter than calculated.
- Usable depth and aging are applied multiplicatively to the 20-hour rated capacity. Lithium is typically 80–90% usable, lead-acid around 50%.
- No temperature correction is applied. Capacity falls below 25°C (roughly −10 to −20% at 0°C) and heat shortens life.
- Manufacturer runtime charts are measured on new batteries at 25°C with a fixed load and a defined cutoff, so a 10–30% difference from this estimate is normal.
Electricity cost and carbon estimate
Average watts and daily hours give daily, monthly and yearly energy. A tariff and emission factor turn that into cost and CO2. The Korea mode applies the three residential tiers with base charge, VAT and the industry fund.
| Daily energy | 3.07 kWh |
|---|---|
| Monthly energy | 93.51 kWh |
| Yearly energy | 1,121.28 kWh |
| Monthly cost | ₩14,685 |
| Yearly cost | ₩176,226 |
| Monthly CO2 | 42.9 kg |
| Yearly CO2 | 514.7 kg |
Korea tier breakdown
| Tier | Energy | Energy charge |
|---|---|---|
| Tier 1: 0–200 kWh | 93.51 kWh | ₩11,221 |
| Tier 2: 201–400 kWh | 0.00 kWh | ₩0 |
| Tier 3: over 400 kWh | 0.00 kWh | ₩0 |
Estimate includes 10% VAT, the 3.7% industry fund and the 9 KRW/kWh climate charge. Real bills vary with season, the summer/winter super-user rate, welfare discounts and contract class.
Emission factors differ by year and agency. Defaults are 459 for Korea, 434 for Japan, 371 for the United States and 495 gCO2/kWh for Taiwan, all editable.
Export
Copy or download the device list and all three results as CSV or Markdown. Everything is generated in the browser and nothing is uploaded.
Preview
section,label,qty,value,unit device,NAS,1,40,W device,Router,1,12,W device,Switch,1,15,W device,Mini PC,1,45,W device,HDD,2,16,W sizing,total_w,,128,W sizing,load_va,,182.9,VA sizing,design_va,,228.6,VA sizing,design_w,,160,W sizing,recommended_va,,350,VA sizing,load_ratio,,36.6,% runtime,battery_wh,,2400,Wh runtime,usable_wh,,1536,Wh runtime,dc_current,,7.82,A runtime,runtime_min,,429,min runtime,target_min,,30,min cost,daily_kwh,,3.07,kWh cost,monthly_kwh,,93.51,kWh cost,yearly_kwh,,1121.28,kWh cost,monthly_cost,,14685,KR cost,yearly_cost,,176226,KR cost,monthly_co2,,42.92,kg cost,yearly_co2,,514.67,kg
How it works
Every calculation finishes inside the browser, and every assumption is written on the page and in the guides.
Frequently asked questions
Should I choose a UPS by VA or by watts?
Look at both. A UPS has a VA ceiling and a watt ceiling, and modern units are usually rated at an output power factor of 0.9 to 1.0. A load with a low power factor needs more VA for the same watts, so picking on VA alone can leave you over the watt limit.
Why do power factor values range from 0.6 to 0.9?
It depends on the load. Cheap adapters without power factor correction sit at 0.5–0.6, ordinary ATX supplies at 0.6–0.7, and active-PFC supplies at 0.9–0.99. Use the nameplate or a PDU measurement when you have it; if not, assume 0.7 and keep more headroom.
How much peak headroom should I leave?
20–30% is typical. If you have repeated short peaks such as drive spin-up, GPU boost or PoE camera boot, go to 30%. Too much headroom (below a 20% load ratio) hurts efficiency and battery life.
Why is the calculated runtime shorter than the vendor chart?
Vendor charts are measured on a new battery at 25°C, often at 50% load, down to a specified cutoff voltage. Aging, low temperature, a high load ratio and inverter losses easily remove 10–30%. A battery older than three years may hold only 60–70% of its rated capacity.
What is the difference between constant power and constant current discharge?
An inverter keeps drawing the same watts as voltage falls, so current rises: that is constant power. A pure resistive load draws current in proportion to voltage: that is constant current. Constant power averages a higher current and therefore a shorter runtime.
How accurate is the Korean electricity bill estimate?
It applies the three residential low-voltage tiers, the base charge, a 9 KRW/kWh climate charge, 10% VAT and the 3.7% industry fund. It does not model the summer/winter super-user rate above 450 kWh, welfare discounts or commercial contract classes, so a real bill can differ by a few thousand won.
Is my device list uploaded anywhere?
No. Everything runs inside your browser, with no server, API or account. Inputs stay in this device's localStorage only, and clearing site data removes them.
UPS and home lab power guides
Sizing, runtime, battery chemistry and electricity cost, in the order you would use them.
- VA, watts and power factor on a UPS nameplateWhy a UPS lists both VA and watts, what a low power factor does to the rating you need, and how to read the numbers.
- Sizing a UPS for a home lab and NASUse real measured watts from your NAS, router, mini PC and switch to choose UPS capacity and headroom without overspending.
- Battery runtime maths and the Peukert effectCalculate backup minutes from Ah, voltage, series and parallel layout, efficiency and depth of discharge, then correct for Peukert.
- UPS batteries: lead-acid versus LiFePO4Compare VRLA and AGM lead-acid with LiFePO4 lithium for UPS use: cycle life, usable depth, temperature, safety and cost.
- Home lab electricity cost and carbonTurn average watts into monthly and yearly cost and CO2, with the Korean tiered tariff and default rates for Japan, the US and Taiwan.