Home lab electricity cost and carbon
In one line: Turn average watts into monthly and yearly cost and CO2, with the Korean tiered tariff and default rates for Japan, the US and Taiwan.
Running a home lab around the clock turns electricity into a visible line item. A single 100 W device uses 72 kWh a month, roughly ten thousand won on a Korean residential bill. Several devices change the picture quickly.
Working out consumption
daily kWh = average W / 1000 * hours
monthly kWh = daily kWh * 30.44
yearly kWh = daily kWh * 365
Average watts means a 24-hour average, not the peak. A NAS that idles at 35 W and peaks at 55 W but idles most of the day should be counted near 38 W. A week of smart plug logging gives the most honest number.
The Korean residential tiers
Residential low-voltage customers are billed in three blocks, and crossing into a higher block applies that block's rate to the whole month's energy, not just the excess. From the October 2024 revision, the energy charges are 120.0 won, 214.6 won and 307.3 won per kWh, with base charges of 910, 1,600 and 7,300 won.
| Monthly use | Energy charge (example) | Base charge | Note |
|---|---|---|---|
| 200 kWh | 24,000 won | 910 won | tier 1 only |
| 300 kWh | 45,460 won | 1,600 won | 200 + 100 at 214.6 |
| 450 kWh | 77,605 won | 7,300 won | 200 + 200 + 50 at 307.3 |
On top of that come a 9 won/kWh climate charge, 10% VAT and a 3.7% industry fund. Adding 100 kWh to a home lab costs about 12,000 won while you are in tier 1, but over 30,000 won once you are in tier 3. Under a progressive tariff the marginal cost of "just a bit more" is much higher than the average.
Rates elsewhere
| Country | Typical rate | Currency | Note |
|---|---|---|---|
| Japan | about 31 | JPY/kWh | varies by amperage and time of day |
| United States | about 0.17 | USD/kWh | wide state and seasonal spread |
| Taiwan | about 4.0 | TWD/kWh | six tiers, 1.68 to 8.46 |
These are averages for households. Real bills vary with season, time-of-use pricing and contract class, so enter the rate from your own bill for anything that matters.
Carbon
Each kWh carries CO2 depending on how it was generated. National grid factors are roughly 459 gCO2/kWh for Korea, 434 for Japan, 371 for the United States and 495 for Taiwan. Running 100 W for a year is 876 kWh, about 402 kg of CO2 in Korea, comparable to driving a car some 1,600 km.
Bringing it down
- Cut idle draw: drive spin-down, CPU governor, shutting down unused VMs. Ten watts saved is 88 kWh a year.
- Schedule: move backups and indexing to cheaper or off-peak hours.
- Consolidate: three mini PCs at 15 W may use more than one efficient 35 W server.
- Efficiency: an 80 PLUS Gold supply, DC-DC power, and removing unnecessary LEDs and fans.
The calculator runs right here in your browser. Your device list is not saved.
Back to the UPS calculatorFrequently asked questions
Does standby power count on the bill?
Yes. Anything plugged in and idling draws 0.5 to 5 W. Five watts is 44 kWh a year, about the same as running a small NAS continuously.
Can I meter a home lab separately in Korea?
Residential premises usually have one meter per household, so separate metering is difficult. A sub-meter tells you the consumption, but the bill is still calculated on the household total.
Which emission factor should I use?
It depends on country, year and agency. Korea publishes grid factors through its power exchange and environment ministry, the US through EPA eGRID, and international comparisons often use IEA. The calculator supplies defaults, but always state the source year in a report.
Sources
Read next
- VA, watts and power factor on a UPS nameplateWhy a UPS lists both VA and watts, what a low power factor does to the rating you need, and how to read the numbers.
- Sizing a UPS for a home lab and NASUse real measured watts from your NAS, router, mini PC and switch to choose UPS capacity and headroom without overspending.
- Battery runtime maths and the Peukert effectCalculate backup minutes from Ah, voltage, series and parallel layout, efficiency and depth of discharge, then correct for Peukert.